@techreport{oai:kanazawa-u.repo.nii.ac.jp:00045912, month = {Sep}, note = {園芸用温室の省エネ除湿技術として,外気との湿度差を駆動源とする吸着式デシカント除湿暖房プロセスを提案した。除湿量は回転数の増加とともに多くなり吸着熱発生量も増加するが,温度上昇度は比較的低い回転数で最大となった。低回転数では,吸着ゾーン途中で吸着破過を生じるために十分な吸着熱が得られず,高回転数では,発生する吸着熱のうちデシカントロータの温度上昇に使われる割合が大きくなる。また,再生空気温度が低下するとロータの全熱交換挙動がより顕著となり昇温幅は減少するが,ロータ出口空気の回転方向分布測定結果から吸着区間の分割が除湿暖房効果の維持に有効であることがわかった。, This study aims to develop the desiccant dehumidification and heating process for agricultural greenhouse. At first, influences of some operating parameters on the adsorption outlet air temperature and humidity were studied. It was found that there were optimum values of the rotation speed and adsorption/regeneration flow ratio at which the temperature in the process outlet air became the largest. Influence of regeneration air temperature on the temperature increase and the amount of adsorption was quite serious since the difference of relative humidity between adsorption and regeneration air became small as the regeneration temperature decreased. Also, the cooled rotor during regeneration step absorbed heat of adsorption which is generated at the beginning of the adsorption zone. Excluding of the low temperature air leaving the beginning of the adsorption zone is useful to obtain higher temperature process outlet air even when the regeneration air temperature is low., 研究課題/領域番号:25660197, 研究期間(年度):2013-04-01 - 2016-03-31, 出典:研究課題「湿度スイング操作型吸着材デシカントロータを用いた施設園芸用温室の除湿暖房」課題番号:25660197 (KAKEN:科学研究費助成事業データベース(国立情報学研究所)) (https://kaken.nii.ac.jp/report/KAKENHI-PROJECT-25660197/25660197seika/)を加工して作成, 金沢大学理工研究域機械工学系}, title = {湿度スイング操作型吸着材デシカントロータを用いた施設園芸用温室の除湿暖房}, year = {2016} }